Running feedback
t
RPM
RPM
NOM
Run detection
Oil pressure
menu 6175
RPM / Oil pressure
Firing speed
Remove starter input
The drawing below shows how the setpoint of the "remove starter input" is detected at the firing speed level.
The factory setting is 400 RPM (6170 Running detect.).
t
RPM
RPM
NOM
Remove starter,
menu 6174
RPM / Oil pressure
Firing speed Running
Run detection
Oil pressure
menu 6175
The remove starter function can use the MPU or a digital input.
6.1.5 Double starter
In some emergency installations, the prime mover is equipped with an extra start motor. Dependent on the
configuration, the "Double starter" function can toggle between the two starters or try several attempts with
the standard starter before switching to the "Double starter".
The "Double starter" function is set up in channel 6191-6192, and a relay for cranking with the alternative
starter is chosen in the configuration of inputs/outputs.