EasyManua.ls Logo

Deif AGC 100 - Regulator Inputs

Deif AGC 100
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Off regulation mode
If off regulation mode is selected, the regulator is not able to do anything. This mode is the default mode. If
this mode is chosen while manual or auto regulation mode is functioning, the output of the regulator will be
frozen and will stay like that after the off regulation mode is not used anymore.
The frozen output can be reset through the following three M-Logic commands:
PID Reg set out to Offset
PID Reg set out to Min
PID Reg set out to Max
These commands are explained in the document "ML-2 application notes M-Logic".
9.1.6 Regulator inputs
It is possible to choose different kinds of inputs for the regulator. The input is scaled to a value between -100
% and 100 %. In this way, the regulator is able to handle many different inputs. The value shown in the dis-
play is always compared to the chosen reference value and is scaled in the same way as the input. In the
table below the different inputs are listed.
AGC 100 Designer's Reference Handbook
4189340766 UK
PID controller (AGC 110 only)
DEIF A/S Page 148 of 152

Table of Contents

Other manuals for Deif AGC 100

Related product manuals