8.5 AGC 145/146 digital inputs
8.5.1 AGC 145/146 digital inputs
The table below shows the available digital input for AGC 145 and AGC 146. Input selections for the genera-
tors are descriped earlier in this document in the chapter "Additional functions" and "Digital inputs".
Input function Auto Semi Test Man Block Configurable Input type
1 Access lock X X X X X Configurable Constant
2 Remote start X X Configurable Pulse
3 Remote stop X X Configurable Pulse
4 Test X X X X Configurable Pulse
5 Auto X X X X Configurable Pulse
6 Remote TB ON (Only AGC 146) X X Configurable Pulse
7 Remote TB OFF (only AGC 146) X X Configurable Pulse
8 Remote MB ON X X Configurable Pulse
9 Remote MB OFF X X Configurable Pulse
10 Remote alarm acknowledge X X X X X Configurable Constant
11 Auto start/stop X Configurable Constant
12 TB position ON (only AGC 146) X X X X X Configurable Constant
13 TB position OFF (Only AGC
146)
X X X X X Configurable Constant
14 MB position ON X X X X X Configurable Constant
15 MB position OFF X X X X X Configurable Constant
16 Emergency stop X X X X X Not configurable Constant
17 Mains Okay X X X X X Configurable Pulse
18 TB close inhibit (Only AGC 146) X X X X Configurable Constant
19 MB close inhibit X X X X X Configurable Constant
20 Enable mode shift X X X X X Configurable Constant
21 Alternative start X X X X X Configurable Constant
22 Switchboard error X X X X X Configurable Constant
23 Total test X X X X X Configurable Constant
24 TB spring loaded (Only AGC
146)
X X X X X Configurable Constant
25 MB spring loaded X X X X X Configurable Constant
8.5.2 Functional description
1. Access lock
Activating the access lock input deactivates the control display push-buttons. It will only be possible to view
measurements, alarms and the log.