2. Remote start
This input initiates the start sequence or plant mode of the gensets from the mains unit, when parameter
8021 is set to remote
3. Remote stop
This input initiates the stop sequence or plant mode of the gensets from the mains unit, when parameter 8021
is set to remote.
4. Test mode
Changes the present running mode to test.
5. Auto mode
Changes the present running mode to auto.
6. Remote TB ON
The tie breaker ON sequence will be initiated and the breaker will close if the mains breaker is opened.
7. Remote TB OFF
The tie breaker OFF sequence will be initiated.
8. Remote MB ON
The mains breaker ON sequence will be initiated.
9. Remote MB OFF
The mains breaker OFF sequence will be initiated.
10. Remote alarm acknowledge
Acknowledges all present alarms, and the alarm LED on the display stops flashing.
11. Auto start/stop
The genset will start when this input is activated. The genset will be stopped if the input is deactivated. The
input can be used when the unit is in island operation, load takeover and the AUTO running mode is selected.
12. Tie breaker closed feedback (TB position ON)
The input function is used as an indication of the tie breaker position. The unit requires this feedback when
the breaker is closed or a position failure alarm occurs.
13. Tie breaker open feedback (TB position OFF)
The input function is used as an indication of the tie breaker position. The unit requires this feedback when
the breaker is opened or a position failure alarm occurs.
14. Mains breaker closed feedback (MB position ON)
The input function is used as an indication of the mains breaker position. The unit requires this feedback
when the breaker is closed or a position failure alarm occurs.
15. Mains breaker open feedback (MB position OFF)
The input function is used as an indication of the mains breaker position. The unit requires this feedback
when the breaker is opened or a position failure alarm occurs.
16. Emergency stop
The input will open the mains breaker in all plant modes. If the generator breaker(s) and the tie/mains breaker
is closed at the same time, the emergency stop will open the mains, tie and generator breaker(s) and shut
down the generator(s) immediately.
AGC 100 Designer's Reference Handbook
4189340766 UK
Power management (AGC 14x only)
DEIF A/S Page 137 of 152