6.25.1 Standard texts
Condition Comment
BLOCK Block mode is activated
SIMPLE TEST Test mode is activated
FULL TEST
SIMPLE TEST ###.#min Test mode activated and test timer counting down
FULL TEST ###.#min
ISLAND MAN Genset stopped or running and no other action taking
place
ISLAND SEMI
READY ISLAND AUTO Genset stopped in Auto
ISLAND ACTIVE Genset running in Auto
AMF MAN Genset stopped or running and no other action taking
place
AMF SEMI
READY AMF AUTO Genset stopped in Auto
AMF ACTIVE Genset running in Auto
LOAD TAKEOVER
MAN
Genset stopped or running and no other action taking
place
LOAD TAKEOVER
SEMI
READY LTO AUTO Genset stopped in Auto
LTO ACTIVE Genset running in Auto
DG BLOCKED FOR
START
Generator stopped and active alarm(s) on the genera-
tor
*Relevant for all var-
iants, except for AGC
110.
BLOCKED FOR START Engine stopped and active alarm(s) on the engine *Only for AGC 110.
GB ON BLOCKED Generator running, GB open and an active "Trip GB"
alarm
SHUTDOWN OVER-
RIDE
The configurable input is active
ACCESS LOCK The configurable input is activated, and the operator
tries to activate one of the blocked keys
GB TRIP EXTERNALLY Some external equipment has tripped the breaker An external trip is log-
ged in the event log
MB TRIP EXTERNALLY Some external equipment has tripped the breaker An external trip is log-
ged in the event log
IDLE RUN The "Idle run" function is active. The genset will not
stop until a timer has expired
IDLE RUN ###.#min The timer in the "Idle run"’ function is active
Aux. test ##.#V ####s Battery test activated
AGC 100 Designer's Reference Handbook
4189340766 UK
Additional functions
DEIF A/S Page 88 of 152