If there are already 16 gensets on the CAN line and a new AGC tries to connect to the plant, an
alarm text, "No IDs available", will appear.
Setup
Stand-
alone:
When the mode menu is set to "Setup Stand-alone", the AGC will change the application
configuration, so it will no longer be a part of the application. When the ID is removed from
the application, the new application will be broadcasted to the other AGCs. The IDs of the
existing gensets in the application will maintain their ID, as a rearrangement could lead to
unnecessary starting and stopping of the gensets.
If the genset that is to be removed is running, it will not be possible/allowed to continue the
process until the genset has stopped. If it is attempted to disconnect, an info text, "Quick set-
up error", will appear.
If "Setup Stand-alone" is activated when the genset is running, an info text, "Quick setup er-
ror", will appear.
If an AGC BTB is detected in the application, an indicating alarm, "Appl. not possible", will ap-
pear.
Change of setup from standard to single DG unit: When disconnecting a standard AGC unit in
a system, it is important to change the menu 9181, plant setup. After disconnecting, the AGC
unit will become a single DG.
8.3.6 9190 Application broadcast
This function makes it possible to broadcast an application over the CAN line from one AGC to all units
present in the application. It can either be done from the display or through the utility software. There are two
ways to broadcast an application:
1. By sending the application.
2. By sending the application and activating it.
Menu 9191: Broadcast application
OFF: When it is set to OFF, no broadcast will be made.
Broadcast: Broadcast of the selected application in menu 9192 will be sent to the units in the applica-
tion.
Broadcast
+ Activate
Broadcast is activated and the application in menu 9192 will be broadcasted and activated
in all units.
Menu 9192: Select which application to be broadcasted
Applications 1-4 can be configured in the utility software.
Through the utility software, it is possible to broadcast and activate the application. Press the broadcast icon
as shown below and mark if the application is to be activated in all controllers. In the broadcast window, the
green arrow shows which application is active.