Simple applications with connection to one mains:
8.3.5 9180 Quick setup
9181 Mode
OFF: When the mode menu is set to "OFF", the existing application that is about to have this genset
included will not look for this new genset. This will give the operator time to connect all wiring
and to do the basic setup of the genset.
Setup
Plant:
When the mode menu is set to "Setup Plant", the new AGC will receive the application config-
uration from the other units in the plant. The new AGC will then notify the rest of the applica-
tion that a new ID is available on the line. If the ID of the new AGC already exists, the new
AGC will – based on the ID numbers in the application configuration – have the highest ID + 1
assigned. This new ID will then be included in the application configuration in all the other
AGCs. During this process, the existing application will be able to continue running and will not
be affected by the upgrade of the system.
The new AGC will automatically go to block mode to ensure that it is in a safe mode. When the
setup is done, the end-user must decide in which running mode the added genset is to run.