Output function Auto Semi Test Man Block Configurable Output type
1 Status OK X X X X X Configurable Constant
2 Run coil X X X X X Configurable Constant
3 Stop coil X X X X X Configurable Constant
4 Stop coil (not activated in start
seq.)
X X X X X Configurable Constant
5 Prepare X X X X X Configurable Constant
6 Starter (Crank) X X X X X Configurable Constant
7 Horn X X X X X Configurable Constant
8 GB on X X X X X Configurable Continuous
9 GB off X X X X X Configurable Continuous
10 MB on X X X X X Configurable Continuous
11 MB off X X X X X Configurable Continuous
6.20.1 Functional description
1. Status OK
2. Run coil
The relay configured to Run coil will be closed the entire time the engine is supposed to run.
3. Stop coil
This relay will close to stop the engine, and when no running feedback is present, it will stay closed in the ext.
stop time (parameter 6212).
4. Stop coil (not activated in start seq.)
The relay configured to this function will do the same as the normal stop coil, with one exception: It will not
close between the start attempts.
5. Prepare
This function will close the relay as the first thing in the start sequence. The relay will be closed for the time
programmed in parameter 6181. This function is used for preheating the engine or for prelubrication.
6. Starter (Crank)
The relay configured to starter will be closed for the time selected in parameter 6184 in the start sequence.
7. Horn
The horn relay is a common alarm output. This means that every time an alarm state appears, the horn relay
will close for the time configured in the parameter 6130 Alarm horn regardless of fail class. If 6130 is set to 0
seconds, it will be on until the reset horn push-button is activated or the alarm(s) has (have) been acknowl-
edged.
8. GB on
The function will close the generator breaker
9. GB off
This function will open the generator breaker
10. MB on
AGC 100 Designer's Reference Handbook
4189340766 UK