EasyManua.ls Logo

Deif AGC 100 - Possibilities; Auxiliary Supply OFF

Deif AGC 100
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.3.7 Possibilities
If one or more units have to be taken out of the power management system, the following possibilities exist
depending on the situation.
8.3.8 Auxiliary supply OFF
The auxiliary supply must be removed from the AGC. This means that a CANbus alarm occurs on the other
AGCs. These alarms appear in a 2 DG plant where ID 2 is powered down:
Alarms Functioning unit (ID 1)
System alarm Failed CAN tx line
System alarm CAN ID 2P/S MISSING (P = Primary CAN, S = Secondary CAN)
Menu 7533 Miss. all units
Menu 7535 Any DG missing
The alarms will be present at all times during the failure. A reconfiguration of the power plant is required to
remove the alarms.
AGC 100 Designer's Reference Handbook
4189340766 UK
Power management (AGC 14x only)
DEIF A/S Page 119 of 152

Table of Contents

Other manuals for Deif AGC 100

Related product manuals