● CAN MAINS X(P/S) MISSING
The AGC unit has lost CANbus communication to the AGC mains unit on CANbus I/F.
● CAN ID X(P/S) MISSING
The AGC unit has lost CANbus communication to one or more CAN IDs on CANbus I/F.
● CAN MAINS X(P/S) MISSING
The AGC unit has lost CANbus communication to the AGC mains unit on CANbus I/F.
● MISSING ALL UNITS
The AGC unit has lost the CANbus communication to all the other units. The fail class set in menu 7533
will be executed.
● FATAL CAN ERROR
The AGC unit has lost CANbus communication to more than one CAN ID on the CANbus line. The fail
class set in menu 7534 will be executed.
● ANY DG MISSING
The AGC unit has lost CANbus communication to one of the generator CAN IDs on the CANbus line. The
fail class set in menu 7535 will be executed.
● ANY MAINS MISSING
The AGC unit has lost CANbus communication to one of the mains CAN IDs on the CANbus line. The fail
class set in menu 7536 will be executed.
● ANY BTB MISSING
The AGC unit has lost CANbus communication to one of the BTB CAN IDs on the CANbus line(s). The
fail class set in menu 7536 will be executed.
8.3.12 CANbus fail class
In menu 7530, it is possible to set a fail class for the following CANbus alarms:
● Missing all units
● Fatal CAN error
● Any DG missing
● Any mains missing
By using these settings, it is possible to disconnect the faulty units and in this way keep the system running in
auto mode (if parameter 7532 is set to "No mode change").
For a general description of "Fail class" please refer to the the chapter Additional functions in
this document.
8.3.13 Limitations
In most cases, the rental applications are very simple applications, and therefore there are some limitations
that have to be considered when using the quick setup menu:
● It will not be possible to have any AGC bus tie units in the application.
This function is made to facilitate change of a plant configuration without AGC BTB units. Entering the quick
setup menu 9180 via the display makes it possible to add or remove a genset without the use of utility soft-
ware. It is only possible to do the same basic setup as through the "application configuration" in the utility
software.
AGC 100 Designer's Reference Handbook
4189340766 UK