Input function Auto Semi Test Man Block Configurable Input type
35 D+ (digital running feedback) X X X X X Configurable Constant
36 Inhibit Engine alarms X X X X X Configurable Constant
6.19.1 Functional description
1. Shutdown override
This input deactivates all protections except the overspeed protection and the emergency stop input. The
number of start attempts is seven by default, but it can be configured in 6180 Start. Also a special cool down
timer is used in the stop sequence after an activation of this input.
2. Access lock
Activating the access lock input deactivates the control display push-buttons. It will only be possible to view
measurements, alarms and the log.
3. Binary running detection
The input is used as a running indication of the engine. When the input is activated, the start relay is deactiva-
ted.
4. Remote start
This input initiates the start sequence of the genset when semi-auto or manual mode is selected.
5. Remote stop
This input initiates the stop sequence of the genset when semi-auto or manual mode is selected. The genset
will stop without cooling down.
6. Test
Changes the present running mode to test.
7. Auto
Changes the present running mode to auto.
. Manual
Changes the present running mode to manual.
9. Block
Changes the present running mode to block.
When block mode is selected, the running mode cannot be changed by activating the digital
inputs.
10. Remote GB ON
The generator breaker ON sequence will be initiated and the breaker will close if the mains breaker is
opened.
11. Remote GB OFF
The generator breaker OFF sequence will be initiated.
12. Remote MB ON
The mains breaker ON sequence will be initiated.