6.19 Digital inputs
The unit has a number of binary inputs, some of which are configurable and some are not.
Input function Auto Semi Test Man Block Configurable Input type
1 Shutdown override X X X X X Configurable Constant
2 Access lock X X X X X Configurable Constant
3 Binary running detection X X X X X Configurable Constant
4 Remote start X X Configurable Pulse
5 Remote stop X X Configurable Pulse
6 Test X X X X Configurable Pulse
7 Auto X X X X Configurable Pulse
8 Manual X X X Configurable Pulse
9 Block X X X X Configurable Constant
10 Remote GB ON X X Configurable Pulse
11 Remote GB OFF X X Configurable Pulse
12 Remote MB ON X X Configurable Pulse
13 Remote MB OFF X X Configurable Pulse
14 Remote alarm acknowledge X X X X X Configurable Constant
15 Auto start/stop X Configurable Constant
16 Remove starter X X X X Configurable Constant
17 GB position ON X X X X X Configurable Constant
18 GB position OFF X X X X X Configurable Constant
19 MB position ON X X X X X Configurable Constant
20 MB position OFF X X X X X Configurable Constant
21 Emergency stop X X X X X Not configurable Constant
22 Low speed X X X Configurable Constant
23 Temperature control X X X Configurable Constant
24 Battery test X X Configurable Pulse
25 Mains Okay X X X X X Configurable Pulse
26 GB close inhibit X X X X Configurable Constant
27 MB close inhibit X X X X X Configurable Constant
28 Enable mode shift X X X X X Configurable Constant
29 Start enable X X X X Configurable Constant
30 Alternative start X X X X X Configurable Constant
31 Switchboard error X X X X X Configurable Constant
32 Total test X X X X X Configurable Constant
33 GB spring loaded X X X X X Configurable Constant
34 MB spring loaded X X X X X Configurable Constant