6.10 Running output
6160 Run status can be adjusted to give a digital output when the genset is running.
Select the correct relay number in output A and output B and enable the function. Change the relay function
to limit in the I/O menu. Then the relay will activate, but no alarm will appear.
If the relay function is not changed to "limit" function, an alarm will appear at every running
situation.