EasyManua.ls Logo

Deif AGC 100 - Running Output

Deif AGC 100
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.10 Running output
6160 Run status can be adjusted to give a digital output when the genset is running.
Select the correct relay number in output A and output B and enable the function. Change the relay function
to limit in the I/O menu. Then the relay will activate, but no alarm will appear.
If the relay function is not changed to "limit" function, an alarm will appear at every running
situation.
AGC 100 Designer's Reference Handbook
4189340766 UK
Additional functions
DEIF A/S Page 60 of 152

Table of Contents

Other manuals for Deif AGC 100

Related product manuals