EasyManua.ls Logo

Deif AGC 100 - Wiring Diagram; Canbus Wiring

Deif AGC 100
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.6 Wiring diagram
8.6.1 CANbus wiring
The following diagrams show examples with three AGC units connected, e.g. one AGC 14x and two genera-
tor AGC units.
AGC 14x
CANbus interface A
53 54 55
H COM L
Multi-line 2
CANbus interface 1/A
A1 A2 A3
H GND L
Multi-line 2
CANbus interface 1/A
A1 A2 A3
H GND L
120 120
AGC 14x
CANbus interface B
57 58 59
H COM L
Multi-line 2
CANbus interface 2/B
B1 B2 B3
H GND L
Multi-line 2
CANbus interface 2/B
B1 B2 B3
H GND L
120 120
AGC 14x
CANbus interface A
53 54 55
H COM L
Multi-line 2
CANbus interface 2/B
B1 B2 B3
H GND L
Multi-line 2
CANbus interface 1/A
A1 A2 A3
H GND L
120 120
As you can see from the last example, it is possible to mix CANbus interface 1 and 2 (or A and B).
For distances above 300 metres, we recommend to use a CAN to fibre converter.
Do not connect the cable shield to the GND/COM terminal of the AGC units.
AGC 100 Designer's Reference Handbook