Sensor type 4 = ESF
RMI sensor type
Fuel level Type 1 Type 2 Type 3 Type 4 Configurable RMI
% Not used
0 78.8 3 240
25 147
50 103
75 60
100 1.6 180 33
If the RMI input is used as a level switch, then be aware that no voltage must be connected to
the input. If any voltage is applied to the RMI inputs, it will be damaged. Please refer to the Ap-
plication Notes for further wiring information.
The configurable type is configurable with eight points in the range 0-2500 Ω. The value as well
as the resistance can be adjusted.
6.21.6 Illustration of configurable inputs
Setpoints
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
Setpoint 5
Setpoint 6
Setpoint 7
8 7 6 54 3 2 1
Value
(bar, °C or %)
Resistance
()
Setpoint 8
AGC 100 Designer's Reference Handbook
4189340766 UK
Additional functions
DEIF A/S Page 82 of 152