Start sequence:
Extended start prepare
t
OFF
t
OFF
1 sec.
2nd start attempt1st start attempt 3rd start attempt
Crank (starter)
Start prepare
Stop coil
Run coil
Running feedback
Run coil can be activated from 1...600 sec. before crank (starter) will be executed. In the above
example, the timer is set to 1 sec. (menu 6150).
3.8.3 Start sequence conditions
The start sequence initiation can be controlled by the following conditions:
Oil pressure (RMI 6,7 or 8)
Water temperature (RMI 6,7 or 8)
Fuel level (RMI 6, 7 or 8)
This means that if e.g. the oil pressure is not primed to the sufficient value, then the crank relay will not en-
gage the starter motor.
The selection is made in setting 6185. For each of the RMI settings, the rule is that the value (oil pressure,
fuel level or water temperature) must exceed the setpoint of setting 6186 before starting is initiated.
If the value in 6186 is set to 0.0, the start sequence is initiated as soon as it is requested.