Section Definition
Static section Part of the total application which is separated by one or two open BTBs. There will be no
closed BTBs within this section.
A static section can also be a dynamic section, but not vice versa.
Dynamic sec-
tion
Part of the total application which is separated by one or two open BTBs. There may be
one or more closed BTBs within this section.
If no BTBs are installed, the application consists of a static section only.
Only use remote start signal in island application with BTB units.
CANbus
G
Diesel generator set 1
Busbar
Controller
Display 1
TB 17
Load
MB 17
G
Diesel generator set 3
Busbar
Controller
Display 3
TB 18
Load
MB 18
G
Diesel generator set 2
Controller
Display 2
BTB 33
BTB 34
Area 1
The area on the left of
BTB 33 is a static section
because it is separated
by the open BTB 33.
The BTB 34 is in closed
position. Therefore the
indicated section is a dy-
namic section.
Please see "Application design" earlier in this document about how to setup applications with
more than one AGC.
8.4.11 Plant mode handling
Basically, six menus are available for setting up the functionality of the application.
AGC 100 Designer's Reference Handbook
4189340766 UK
Power management (AGC 14x only)
DEIF A/S Page 129 of 152