This function will close the mains breaker
11. MB off
This function vil open the mains breaker
6.21 Multi-inputs
The AGC unit has three multi-inputs which can be configured to be used as the following input types:
1. 4 to 20 mA
2. RMI oil
3. RMI water
4. RMI fuel
5. Binary
6. Pt1000
The function of the multi-inputs can only be configured in the PC utility software. The parame-
ters to change the configuration of the multi-inputs are 10980, 10990 and 11000.
For each input, two alarm levels are available, the menu numbers of the alarm settings for each multi-input is
controlled by the configured input type as seen in the following table.
Input type Multi-input 6 Multi-input 7 Multi-input 8
4 to 20 mA 4120/4130 4250/4260 4380/4390
RMI oil 4180/4190 4310/4320 4440/4450
RMI water 4200/4210 4330/4340 4460/4470
RMI fuel 4220/4230 4350/4360 4480/4490
Binary 3400 3410 3420
Pt1000 4160/4170 4290/4300 N/A
Only one alarm level is available for the digital input type.
The USW only shows the parameter from the selected multi-input. The multi-input is by default set to binary,
which means that the only alarm parameters available are 3400, 3410 and 3420. If you want to read the
alarms from RMI oil 6, you have to change parameter 10980 to RMI oil 6, when reading the parameters from
the device, before you get access to the alarm parameters.
6.21.1 4-20 mA
If one of the multi-inputs has been configured as 4-20 mA, the unit and range of the measured value corre-
sponding to 4-20 mA can be changed in the PC utility software in order to get the correct reading in the dis-
play.
6.21.2 RMI inputs
The unit can contain up to three RMI (resistance measurement input). The inputs have different functions, as
the hardware design allows for several RMI types.
RMI is a resistance measurement input which can be used together with a resistance dependant sensor.
These various types of RMI are available for all multi-inputs:
RMI oil: Oil pressure
AGC 100 Designer's Reference Handbook
4189340766 UK
Additional functions
DEIF A/S Page 79 of 152