6.11.8 Stop
Start
Temp control
OFF
End
No
Auto
start/stop
OFF
No
Yes
Idle timer on
Yes
Lowspeed ON
Genset stop
sequence
Idle timer
expired
Genset running
at idle speed
No
Yes
No
Yes
Yes
Genset running
at idle speed
Genset stop
sequence
No
6.12 Engine heater
This function is used to control the temperature of the engine. A sensor measuring the cooling water tempera-
ture is used to activate an external heating system to keep the engine at a minimum temperature.
The setpoints adjusted in menu 6320 are:
Setpoint: This setpoint +/- the hysteresis is the start and stop points for the engine heater.
Output A: The relay output for the engine heater.
Input type: Multi-input to be used for temperature measurement.
AGC 100 Designer's Reference Handbook
4189340766 UK
Additional functions
DEIF A/S Page 65 of 152