EasyManua.ls Logo

Deif AGC 100 - Run Status (6160)

Deif AGC 100
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The timer in 6160 is not used if binary running feedback is used.
Inhibit of the alarm is active as long as one of the selected inhibit functions is active.
Example:
In this example, inhibit is set to Not run status and GB ON. Here, the alarm will only be active when the gen-
erator is running and disabled again when the GB is closed.
6.6.1 Run status (6160)
Alarms can be adjusted to activate only when the running feedback is active and a specific time delay has
expired.
The diagram below illustrates that after activation of the running feedback, a run status delay will expire.
When the delay expires, alarms with Run status will be activated.
AGC 100 Designer's Reference Handbook
4189340766 UK
Additional functions
DEIF A/S Page 55 of 152

Table of Contents

Other manuals for Deif AGC 100

Related product manuals