Selections for alarm inhibit:
Function Description
Inhibit 1 M-Logic outputs: Conditions are programmed in M-Logic
Inhibit 2
Inhibit 3
GB ON (TB ON) The generator breaker is closed
GB OFF (TB ON) The generator breaker is open
Run status Running detected and the timer in menu 6160 expired
Not run status Running not detected or the timer in menu 6160 not expired
Generator voltage > 30% Generator voltage is above 30% of nominal
Generator voltage < 30% Generator voltage is below 30% of nominal
MB ON The mains breaker is closed
MB OFF The mains breaker is open
AGC 100 Designer's Reference Handbook
4189340766 UK
Additional functions
DEIF A/S Page 54 of 152