The configurable type is configurable with eight points in the range 0-2500 Ω. The resistance as
well as the pressure can be adjusted.
If the RMI input is used as a level switch, then be aware that no voltage must be connected to
the input. If any voltage is applied to the RMI inputs, it will be damaged. Please refer to the Ap-
plication Notes for further wiring information.
6.21.4 RMI water
This RMI input is used for measuring the cooling water temperature.
Sensor type 1 = VDO
Sensor type 2 = VDO
Sensor type 3 = VDO
Sensor type 4 = EST-250
RMI sensor type
Temperature Type 1 Type 2 Type 3 Type 4 Configurable RMI
°C °F
20.3 68.4 2500
30 86 1594
40 104 291.5 480.7 69.3 1029
50 122 197.3 323.6 680
60 140 134.0 222.5 36.0 460
70 158 97.1 157.1 321
80 176 70.1 113.2 19.8 227
90 194 51.2 83.2 164
100 212 38.5 62.4 11.7 120
110 230 29.1 47.6 89
120 248 22.4 36.8 7.4 74
130 266 28.9 52
140 284 22.8 40
150 302 18.2
The configurable type is configurable with eight points in the range 0-2500 Ω. The temperature
as well as the resistance can be adjusted.
If the RMI input is used as a level switch, then be aware that no voltage must be connected to
the input. If any voltage is applied to the RMI inputs, it will be damaged. Please refer to the Ap-
plication Notes for further wiring information.
6.21.5 RMI fuel
This RMI input is used for the fuel level sensor.
Sensor type 1 = VDO
Sensor type 2 = VDO
AGC 100 Designer's Reference Handbook
4189340766 UK