In island mode any running mode (MAN, AUTO, SEMI, BLOCK) can be selected on the generator units, and
the remote start signal is still working for the remaining AGC which is still in AUTO mode.
Parallel to mains mode
In load takeover, mains power export and fixed power mode the "auto start/stop" input on the mains unit must
be used for starting the plant.
8.4.6 Plant operation
The table shows how the plant is started:
Plant mode Selection Local Remote
Island mode Display on generator units Auto start/stop on gen. units
Fixed power mode Display on mains unit Auto start/stop on mains unit
Mains power export Display on mains unit Auto start/stop on mains unit
Load takeover Display on mains unit Auto start/stop on mains unit
In peak shaving and AMF the automatic operation starts automatically depending on the impor-
ted power (peak shaving) or mains failures (AMF).
8.4.7 Timer selection
The operation of the plant is controlled by up to eight internal command timers which are programmed using
the PC utility software (USW).
The function can be used in load takeover, mains power export and fixed power, and the mains unit has to be
in auto.
AGC 100 Designer's Reference Handbook
4189340766 UK
Power management (AGC 14x only)
DEIF A/S Page 125 of 152