6.17.3 Engine stopped
Fail class Action Block engine start Block MB sequence Block GB sequence
1 Block X
2 Warning
3 Trip GB X X
4 Trip + stop X X
5 Shutdown X X
6 Trip MB X
7 Trip MB/GB (X) X (X)
In addition to the actions defined by the fail classes, it is possible to activate one or two relay
outputs if additional relays are available in the unit.
The fail class "Trip MB/GB" will only block engine start and GB sequence if no mains breaker is
present.
6.17.4 Fail class configuration
The fail class can be selected for each alarm function either via the display or the PC software.
To change the fail class via the PC software, the alarm function to be configured must be selected. Select the
desired fail class in the fail class roll-down panel.
AGC 100 Designer's Reference Handbook
4189340766 UK
Additional functions
DEIF A/S Page 72 of 152