No. Setting Min. setting Max. setting Factory setting
8181 MB failure start Enable OFF ON OFF
8182 Parallel Enable OFF ON OFF
8183 No break transfer Enable OFF ON OFF
8184 Auto switch Enable OFF Static Dynamic All OFF
8185 Run type Run one/all mains Run all mains Run one mains Run one mains
8186 Run type ID to run 17 32 17
MB close failure start:
This setting determines whether a start of the DGs should be executed if an MB close failure occurs.
If "MB close failure start" is activated, the mode shift functionality will automatically be ena-
bled.
In peak shaving, fixed power, mains power export and load takeover, the function is only active
when menu 7081 Mode shift is set to ON.
MB parallel:
This setting determines whether the mains connections (MBs) should be able to run in parallel or not.
The setting of "MB parallel" affects the function of the "Auto switch" setting.
No break transfer:
This setting determines whether switching between the mains connections (MBs) should be executed as a
black coupling or a synchronised coupling.
If the TBs in a section are adjusted to normally closed and "MB parallel" is switched OFF, then only one of the
TBs can be closed at the time.
The system will try to keep the ID selected in menu 8186 ("My ID to Run") to keep its TB closed. If, however,
the selected ID does not have a TB configured as a normally closed breaker, or if it fails to close it, it will be
the mains unit holding the lowest ID without TB failures present that will close.
If "My ID to Run" is changed during operation, then the MB parallel setting will decide whether a black or a
synchronised change-over will take place.
If "MB parallel" is activated, the "No break transfer" will automatically be enabled.
Auto switch:
This setting determines whether a mains unit detecting a mains failure will try to get the connected load sup-
plied by another mains or by the available DGs.
AGC 100 Designer's Reference Handbook
4189340766 UK
Power management (AGC 14x only)
DEIF A/S Page 130 of 152