Remember to write the settings when changing the I/O configuration.
Channel Menu text Explanation
6191 Standard attempts Accepted total number of start attempts before a "start failure" alarm is ac-
tivated
6192 Double attempts The number of start attempts before redirecting the start signal
The "Double starter" function is enabled by choosing a value higher than zero in channel 6192. This value
determines the amount of attempts on each starter before switching to the next. The "standard starter" has
first priority. When the maximum allowed number of attempts, defined in channel 6191, is reached, the start
attempts stop and the alarm "Start failure" appears.
- A value of 1 in channel 6192 results in a toggle function with 1 attempt on each starter between toggling.
- A value of 2 in channel 6192 results in a toggle function with 2 attempts on each starter between toggling.
AGC 100 Designer's Reference Handbook
4189340766 UK
Additional functions
DEIF A/S Page 50 of 152