Breaker options Description Comments
Mains breaker op-
tions
Select between:
● Pulse
● Ext/ATS control
● Continuous NE
● Compact
● Continuous ND
Depending on the application, select either "Continuous NE"
or "Continuous ND" if mains breaker closure is desired even if
AGC power is removed
Tie breaker op-
tions
Select between:
● Pulse
● Continuous NE
● Compact
● Normally open
● Normally closed
In applications with tie breaker control, it is neces-
sary to use a normally closed (NC) breaker if fixed
power, mains power export or peak shaving is
used.
When the application has been configured write the drawing(s) to the device using the icon.
To activate an application through the utility software, press the icon shown in the picture below and select
which application to activate. The green arrow shows the currently active application.