Table 16. Location requirements (continued)
Criteria Definition
Air quality
v Place the library in an area with minimal sources of particulate contamination.
v Avoid areas near frequently used doors and walkways, stacks of supplies that
collect dust, printers, and smoke-filled rooms.
v Excessive dust and debris can damage tapes and tape drive.
Technical specifications for this library can be referenced in the following tables.
Physical specifications
Table 17. Physical specifications
Characteristic Product alone Packaged
Height 133 mm 694 mm
Width 480 mm
1
667 mm
Depth 873 mm 1194 mm
Weight Base module: 21 Kg
Expansion module: 13 Kg
Base module: 30 Kg
Expansion module: 23 Kg
1
Includes front covering of rack rails, allowing for magazine opening clearance.
Electrical specifications
Table 18. Electrical specifications
Characteristic Specification
Current 5.0 - 3.5 A
Voltage 100 - 240 V 50/60 Hz
Power 350 W
Equipment environmental specifications
Table 19. Equipment environmental specifications
ML3 Operating environment Product power off
Dry bulb
temperature
(deg C)
Relative Humidity
(%RH, non-
condensing)
Max wet
bulb
tempera-
ture
(deg C)
Max
elevation
(meters)
Dry bulb
tempera-
ture
(deg C)
Relative
Humidity
(%RH,
non-
condens-
ing)
Max wet
bulb
tempera-
ture
(deg C)
Allowable Recom-
mended
Allowable Recom-
mended
26 3050 5 to 45 8 to 80 26
15 to 32 16 to 25 20 to 80 20 to 50
Notes:
v Derate maximum dry-bulb temperature 1°C/300 in (34°F/984 ft.) above 900 m (2,953 ft.).
v Derate maximum recommended dry-bulb temperature 1°C/300 in (34°F/984 ft.) above 1,800 m (5,905 ft.).
24 Dell EMC ML3 Tape Library: User's Guide
|
|