7-27
7
UPS Operation
7.2.6 Battery Mode Turn-off Procedures (Parallel)
y
Press the OFF button of one of the parallel UPSs for three to ten seconds and re-
lease it after you hear one beep. The LCD shows the message: ‘SHUTDOWN UPS?’.
Select ‘YES’ and press the function key below the symbol
WRFRQ¿UP\RXUVHOHF-
tion.
1. If the remaining parallel UPSs’ total capacity exceeds the total critical loads, the
inverter of the UPS that you turned off will automatically shut down, and the critical
loads will be equally shared by the remaining parallel UPSs.
The status of the LCD and LEDs for the UPS that you turned off:
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
UNIT : #1.1
LOAD NOT POWERED
TO BROWSE EVENT
(004)
PRESS
Fault
The status of the LCD and LEDs for the remaining parallel UPSs:
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
UNIT : #1.1
LOAD PROTECTED
ON BATTERY
TO BROWSE EVENT
(004)
PRESS
Fault
1
Switch off the Output Switch (Q4) of the UPS that you turned off, and wait until the
UPS’s power module finishes discharging. During the discharging process, the
Inverter Start-up LED
LOOXPLQDWHV$IWHUWKHSRZHUPRGXOH¿QLVKHVGLVFKDUJLQJ
the Inverter Start-up LED
is off.