EasyManua.ls Logo

Det-Tronics Eagle Quantum Premier - EQ3 XXX Controller; Section 6 - Specifications

Det-Tronics Eagle Quantum Premier
142 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
95-8533
6-1
18.2
Section 6
Specifications
NOTE
For USCG Approved System
specications, refer to Appendix D.
EQ3XXX CONTROLLER
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 Vdc. 10%
overvoltage will not cause damage to the
equipment.
INPUT POWER—
9 watts nominal, 12 watts maximum.
LON COMMUNICATION—
Digital communication, transformer isolated
(78.5 kbps).
RS-485 COMMUNICATION—
Modbus Master/Slave capability.
Digital communication, transformer isolated
(up to 115 kbps).
RS-232 COMMUNICATION—
S³ configuration only.
Digital communication, optically isolated.
CONTROLNET—
Digital communication, transformer isolated
(5 Mbps).
ETHERNET DLR—
10/100 Mbps EtherNet DLR capability.
ETHERNET INTERFACE BOARD—
RS-485 Communication: Modbus master/
slave capability, ground fault monitored.
Digital communication, transformer isolated
(up to 230 kbps).
10/100 Mbps BASE-T Ethernet Communication:
Modbus TCP master/slave or S³ configuration
capability.
10/100 Mbps BASE-T Ethernet Communication:
Modbus TCP master/slave capability.
High Speed Serial Link (HSSL): Port used
only for redundant controller to controller
communication.
SERIAL INTERFACE BOARD—
RS-485 Communication: Modbus master/
slave capability, ground fault monitored.
Digital communication, transformer isolated
(up to 230 kbps).
RS-232 Communication: Modbus master/
slave or S³ configuration capability.
Digital communication, non-isolated (up to
230 kbps).
RS-232 Communication: Modbus master/
slave capability.
Digital communication, non-isolated (up to
230 kbps).
High Speed Serial Link (HSSL): Port used
only for redundant controller to controller
communication.
UNSUPERVISED OUTPUTS—
Dry Contact Rating: 1 ampere at 30 Vdc
maximum. SPDT normally open/normally
closed contact, Configurable for normally
energized or de-energized (de-energized is
the default mode).
UNSUPERVISED INPUTS—
Two State input (on/off). User selectable
normally open or normally closed contact
(N.O. is the default).
TROUBLE OUTPUT—
SPDT normally open/normally closed contact,
Non-Configurable, normally energized only.
TEMPERATURE RANGE—
Operating (Certified Rating):
See Certification section below.
Storage: –40°F to +185°F (–40°C to +85°C).
Excluding communication port optional
modules.
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
VIBRATION—
FM 3260, FM 6310/6320.
DIMENSIONS—
See Figure 6-1.
SHIPPING WEIGHT—
5 pounds (2.3 kilograms).