95-8533
6-1
18.2
Section 6
Specifications
NOTE
For USCG Approved System
specications, refer to Appendix D.
EQ3XXX CONTROLLER
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 Vdc. 10%
overvoltage will not cause damage to the
equipment.
INPUT POWER—
9 watts nominal, 12 watts maximum.
LON COMMUNICATION—
Digital communication, transformer isolated
(78.5 kbps).
RS-485 COMMUNICATION—
Modbus Master/Slave capability.
Digital communication, transformer isolated
(up to 115 kbps).
RS-232 COMMUNICATION—
S³ configuration only.
Digital communication, optically isolated.
CONTROLNET—
Digital communication, transformer isolated
(5 Mbps).
ETHERNET DLR—
10/100 Mbps EtherNet DLR capability.
ETHERNET INTERFACE BOARD—
RS-485 Communication: Modbus master/
slave capability, ground fault monitored.
Digital communication, transformer isolated
(up to 230 kbps).
10/100 Mbps BASE-T Ethernet Communication:
Modbus TCP master/slave or S³ configuration
capability.
10/100 Mbps BASE-T Ethernet Communication:
Modbus TCP master/slave capability.
High Speed Serial Link (HSSL): Port used
only for redundant controller to controller
communication.
SERIAL INTERFACE BOARD—
RS-485 Communication: Modbus master/
slave capability, ground fault monitored.
Digital communication, transformer isolated
(up to 230 kbps).
RS-232 Communication: Modbus master/
slave or S³ configuration capability.
Digital communication, non-isolated (up to
230 kbps).
RS-232 Communication: Modbus master/
slave capability.
Digital communication, non-isolated (up to
230 kbps).
High Speed Serial Link (HSSL): Port used
only for redundant controller to controller
communication.
UNSUPERVISED OUTPUTS—
Dry Contact Rating: 1 ampere at 30 Vdc
maximum. SPDT normally open/normally
closed contact, Configurable for normally
energized or de-energized (de-energized is
the default mode).
UNSUPERVISED INPUTS—
Two State input (on/off). User selectable
normally open or normally closed contact
(N.O. is the default).
TROUBLE OUTPUT—
SPDT normally open/normally closed contact,
Non-Configurable, normally energized only.
TEMPERATURE RANGE—
Operating (Certified Rating):
See Certification section below.
Storage: –40°F to +185°F (–40°C to +85°C).
Excluding communication port optional
modules.
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
VIBRATION—
FM 3260, FM 6310/6320.
DIMENSIONS—
See Figure 6-1.
SHIPPING WEIGHT—
5 pounds (2.3 kilograms).