95-8533
4-21
18.2
DCIO Startup
1. The Power-on LED should be illuminated.
The Fault LED should blink once on power
up, then remain off.
2. The input circuits should indicate the
proper state of the input device (channel
active LED illuminates when the circuit is
closed). Check the input power supply and
associated wiring. Verify proper voltage per
the Troubleshooting matrix.
3. The output circuits should indicate the
proper state for the programmed device
(channel active LED illuminates when the
circuit is active). Check the power supply
and associated wiring. Verify proper voltage
per the Troubleshooting matrix.
4. The circuits should not indicate a fault
condition (channel fault LED illuminates
when the circuit is in fault). Check the end-
of-line devices and associated wiring. Verify
proper voltage per the Troubleshooting
matrix.
5. Test the entire system for proper operation
to ensure that the configuration was
performed properly.
Relay Module Startup
1. The Power-on LED should be illuminated.
The Fault LED should blink once on power
up, then remain off.
2. The output circuits should indicate the
proper state for the programmed device
(channel active LED illuminates when the
circuit is active).
3. Test the entire system for proper operation
to ensure that the configuration was
performed properly.
Analog Input Module Startup
1. The Power-on LED should be illuminated.
The Fault LED should blink once on power
up, then remain off.
2. The input circuits should indicate the proper
state for the programmed device (channel
active LED illuminates when the circuit is
active).
3. The circuits should not indicate a fault
condition (channel fault LED illuminates
when the circuit is in fault).
4. Test the entire system for proper operation
to ensure that the configuration was
performed properly.