4-18
95-8533
18.2
Ground Fault Monitor
Verify earth ground connections as specified in
the wiring instructions.
Check power distribution to ensure that all
devices are receiving power.
DCUs
Verify correct address setting.
Check modules for correct orientation.
Check for the presence of contaminants or
poisoning agents.
Device should be oriented with the sensor
pointing down.
IDCs
Verify correct address setting.
Check for correct installation of EOL resistors.
ARMs
Verify correct address setting.
Check jumpers.
SAMs
Verify correct address setting.
Check signal circuits for correct polarity.
Check for correct installation of EOL resistors.
Check jumpers.
NOTE
Please reference EQP Large Scale
Installation manual (95-8770) for more
information on legac products, including
DCUs, IDCs, ARMs, and SAMs.
GENERAL START-UP PROCEDURES
1. Output loads that are controlled by the
system should be secured (remove
power from all output devices) to prevent
actuation.
2. Check all system wiring for proper
connection.
3. Inspect all devices to verify that they
have not been physically damaged in
shipment.
4. Apply power to the system.
NOTE
To prevent the network modules from
going into a fault isolation condition,
apply power to the EQP Controller
prior to applying power to the network
devices.
5. Program the system for the desired
operation using Det-Tronics Safety System
Software (S
³
). Download configuration data
to all devices.
NOTE
After system configuration has been
completed, the entire system should be
tested for proper operation to ensure that
conguration was performed properly.
6. Calibrate the sensors.
7. Ensure that all trouble and alarm conditions
have been cleared and the EQP Controller
is reset, then remove mechanical blocking
devices (if used) and restore power to the
output loads.

Table of Contents