4-20
95-8533
18.2
EDIO Startup
1. The Power-on LED should be illuminated. The
Fault LED should blink once on power up, then
remain off.
2. The input circuits should indicate the proper
state of the input device (channel active LED
illuminates when the circuit is closed). Check
the input power supply and associated wiring.
Verify proper voltage per the Troubleshooting
matrix.
3. The output circuits should indicate the
proper state for the programmed device
(channel active LED illuminates when the
circuit is active). Check the power supply and
associated wiring. Verify proper voltage per
the Troubleshooting matrix.
4. The circuits should not indicate a fault
condition (channel fault LED illuminates when
the circuit is in fault). Check the end-of-line
devices and associated wiring. Verify proper
voltage per the Troubleshooting matrix.
5. Test the entire system for proper operation to
ensure that the configuration was performed
properly.
STARTUP PROCEDURE FOR
DCIO MODULE
Conguration
The DCIO Module is an eight-channel device.
Each channel is capable of being configured
as an input or output, independent of any other
channel.
NOTE
The module is configured using
Det-Tronics Safety System Software.
Activation Time
Timers are made available for output circuits
only. Timers are used primarily to set the timing
of output release in a suppression system.
Timers provide a pulse timed output for the
time period specified in the configuration of the
channel. The channel output goes active when
commanded by the system logic and remains
on until the timer expires.
Static Logic Mode
Each input channel can be configured as a
Fire Alarm, Trouble, Low Gas Alarm, High
Gas Alarm, Supervisory, or Other type of
channel, independent of any other channel
configuration. The type selected determines
the logic the system uses to configure
Indicators, Alarms, and Messages.
For example: When an input is selected as
Fire type, the Fire LED on the Controller and
Audible alarm will automatically actuate when
that input channel is active.