95-8533
6-13
18.2
EQ3750 ASH ADDRESSABLE
SMOKE & HEAT MODULE
For complete information regarding the ASH
Module, refer to instruction manual number
95-8654.
EQ3760ASM ADDRESSABLE
SMOKE MODULE
For complete information regarding the ASM
Module, refer to instruction manual number
95-8755.
COMBUSTIBLE GAS SENSOR
Refer to the Combustible Gas Sensor
Specification Data sheet, form 90-1041, for
specifications.
ELECTROCHEMICAL
SENSORS
Refer to the Electrochemical Gas Sensor
Specifications in the UD10DCU manual (95-
8656) and EQ22xxDCU Specification Data (90-
1118) for additional information.
EQ21XXPS POWER SUPPLY
The EQ21xxPS Rectifier / Power Supply has
many inherent advantages such as voltage
regulation, high efficiency, high power factor
and short circuit protection.
These chargers provide separate adjustable
voltages for floating or equalizing lead or
nickel-cadmium cells. An equalize switch is
located on the front panel of the charger for
manual activation or a multi-mode electronic
timer can be used for automatic activation.
Steady state output voltage remains within
+/- 1/2% of the setting from no load to full load
and for AC input voltages within +/- 10% of the
nominal input voltage. The power supply is
internally filtered to be no greater than 32dBrn
(ā€œCā€ message weighting) and 30 millivolts RMS
for all conditions on input voltage and output
load with or without batteries connected.
This allows the A36D to be used as a battery
eliminator.