2-10
95-8533
18.2
U5015 Explosion Proof Smoke Detector
The Det-Tronics SmokeWatch
TM
U5015
Explosion-Proof Smoke Detector has Division
and Zone explosion-proof ratings and is suitable
for industrial and commercial applications. It is
designed to operate effectively with smoldering
and rapidly growing fires. Outputs include a
localized LED, 0-20mA, and relays.
X7050 xWatch
®
Explosion-Proof Camera
The xWatch high resolution color camera
operates in an explosion–proof enclosure and
can be used to view an area in alarm or to
record activity in an area. It can be used as
a stand-alone unit or attached to any of the
X-series flame detectors. Users have an option
to include a digital video recorder (DVR) as
part of the solution to capture a digital video of
hazard events.
EQ3730EDIO Enhanced Discrete Input/
Output Module
The 8 Channel EDIO Module (see Figure 2-10)
expands the Input and Output capability of the
Eagle Quantum Premier System.
The unit is designed to provide continuous
and automated fire/gas protection, while
ensuring system operation through continuous
supervision of System Inputs/Outputs.
The EDIO module provides eight channels of
configurable input or output points that can be
programmed for supervised or unsupervised
operation. Each input point can accept fire
detection devices such as heat, smoke, or
unitized flame detectors. Each output point
can be configured for signaling or releasing
output operation. Each channel on the module
is provided with individual indicators for active
and fault conditions.
IMPORTANT
For Class A wiring, two input/output
channels are combined, thereby
supporting up to four input/output
circuits.
NOTE
An input must be active for at least 750
milliseconds in order to be recognized.
The EDIO module can be mounted directly to
a panel, or it can be DIN rail mounted. System
status can be determined using the trouble-
shooting procedures, Eagle Quantum Safety
System Software (S
³
) and the status indicators
on the module.
Refer to the Enhanced Discrete Input/Output
Module Specification Data sheet (form number
90-1189) for additional information.
Figure 2-10—Enhanced Discrete
Input/Output Module