6-12
95-8533
18.2
CERTIFICATION—
FM / CSA: Class I, Div. 1, Groups B, C, D.
Class I, Zone 1, Group IIC.
Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4 ).
Class II/III, Div. 1 & 2 (for use
with Model STB).
NEMA/Type 4X (for use
with Model STB).
Refer to Appendix A for FM Approval details.
Refer to Appendix B for CSA Approval details.
ATEX: 0539
FM
APPROVED
®
II 2 G
Ex db IIC T4-T6 EN 60079-29-1
DEMKO 02 ATEX 131321X
T6 (Tamb = –55°C to +50°C)
T5 (Tamb = –55°C to +65°C)
T4 (Tamb = –55°C to +75°C)
IP66
Refer to Appendix C for ATEX Approval details.
Special Conditions for Safe Use (X):
The device has an ambient temperature rating
for performance of –40°C to +75°C.
IEC: IECEx ULD 10.0010
Ex d IIC T4-T6 Gb
T6 (Tamb = –55°C to +50°C)
T5 (Tamb = –55°C to +65°C)
T4 (Tamb = –55°C to +75°C)
Refer to Appendix D for USCG Approval
details.
Refer to Appendix E for CE Mark details.
EQ24xxNE NETWORK
EXTENDER
INPUT VOLTAGE—
24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage
will not cause damage to the equipment.
POWER CONSUMPTION—
2.2 watts nominal at 24 Vdc, 2.7 watts
maximum.
INPUTS/OUTPUTS—
Digital, transformer isolated (78.5k Baud).
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C)
Storage: –67°F to +185°F (–55°C to +85°C).
HUMIDITY—
5 to 95% RH at 70°C.
DIMENSIONS—
See Figure 6-7.
CERTIFICATION—
FM / CSA: Class I, Div. 1, Groups B, C, D.
Class I, Zone 1, Group IIC.
Class II/III, Div. 1, Groups E, F, G.
Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4 ).
Class II/III, Div. 2, Groups F & G (T4).
NEMA/Type 4X.
Refer to Appendix A for FM Approval details.
Refer to Appendix B for CSA Approval details.
CE: ATEX/EMC Directive Compliant.
ATEX:
0539
FM
APPROVED
II 2 G.
Ex db IIC T4-T6
DEMKO 02 ATEX 131321X
T6 (Tamb = –55°C to +50°C)
T5 (Tamb = –55°C to +65°C)
T4 (Tamb = –55°C to +75°C)
IP66
Refer to Appendix C for ATEX Approval details.
IEC: IECEx ULD 10.0010
Ex d IIC T4-T6 Gb
T6 (Tamb = –55°C to +50°C)
T5 (Tamb = –55°C to +65°C)
T4 (Tamb = –55°C to +75°C)
Refer to Appendix D for USCG Approval
details.
Refer to Appendix E for CE Mark details.
FM
APPROVED
®
FM
APPROVED
®
FM
APPROVED
®
FM
APPROVED
®
3.46
(8.8)
4.7
(11.9)
2.7
(6.9)
5.2
(13.2)
5.86
(14.9)
A2531
3.77
(9.6)
1.28
(3.3)
Figure 6-7—Dimensions of Short Cover Junction Box
in Inches (Centimeters)