95-8533
2-13
18.2
EQ3760ASM Addressable Smoke & Heat
Module
The EQ3760ASM Addressable Smoke &
Heat Module (see Figure 2-15) is an interface
device designed to provide continuous and
automated fire protection for the EQP system.
The EQ3760ASM is located directly on the
LON of the EQP system, with a loop of up
to 100 addressable devices tied into the
EQ3760ASM. This allows all of the flame, gas,
and addressable smoke and heat detectors
to run on one system, enabling the EQP
controller to annunciate a fire alarm from either
its own LON based I/O, or from the connected
addressable smoke and heat detection loops.
The EQP controller can support up to 10
EQ3760ASM modules.
The EQ3760ASM can support a variety of
Apollo Discovery and XP95 devices, including
smoke, heat, manual call, sounders, beacons
and I/O modules. The addressable devices are
configured individually via the S
³
software.
To ensure reliable system operation, the
EQ3760ASM continuously monitors its input
and output circuits for opens and short circuit
conditions.
During normal operation, the EQ3760ASM
continuously checks the loop for fault
conditions and executes user defined
programmed logic that coordinates the control
of the field devices. The EQ3760ASM reports
any device based fault and alarm conditions to
the EQP controller.
The EQP Controller continuously monitors the
status of the EQ3760ASM, as well as the status
of each device connected to the EQ3760ASM.
The EQ3760ASM's alarm and fault status
conditions are logged in the EQP controller.
System status can be determined using
S
³
software or the status indicators on the
EQ3760ASM, where LEDs annunciate power
on, faults, or an active device on the loop.
Refer to the EQ3760ASM instruction manual
(form number 95-8755) for additional
information.
EQ3750ASH Addressable Smoke & Heat
Module
The Addressable Smoke and Heat (ASH)
Module (see Figure 2-16) is an interface
device designed to provide continuous and
automated fire protection for the EQP system.
The ASH module is located directly on the
LON of the EQP system, with a loop of up to
64 addressable devices tied into the ASH
module. This allows all of the flame, gas, and
addressable smoke and heat detectors to run
on one system, enabling the EQP controller to
annunciate a fire alarm from either its own LON
based I/O, or from the connected addressable
smoke and heat detection loops. The EQP
controller can support up to 10 ASH modules.
The ASH module can support a variety of
Apollo Discovery and XP95 devices, including
smoke, heat, manual call, sounders, beacons
and I/O modules. The addressable devices are
configured individually via the S
³
software.
To ensure reliable system operation, the ASH
module continuously monitors its input and
output circuits for opens and short circuit
conditions.
During normal operation, the ASH module
continuously checks the loop for fault
conditions and executes user defined
programmed logic that coordinates the control
of the field devices. The ASH module reports
any device based fault and alarm conditions to
the EQP controller.