EDR-3000 IM02602003E
Parameter Description Setting range Default Menu path
Force RO2 By means of this function the normal Relay Output State
can be overwritten (forced). The relay can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
Normal,
De-Energized,
Energized
Normal [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-3ZI X2]
Force RO3 By means of this function the normal Relay Output State
can be overwritten (forced). The relay can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
Normal,
De-Energized,
Energized
Normal [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-3ZI X2]