EasyManua.ls Logo

Eaton EDR 3000 - Current and Ground Current Measurement

Eaton EDR 3000
770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-3000 IM02602003E
Current and Ground Current Measurement
Plug-in Connector with Integrated Short-Circuiter
(Conventional Current Inputs)
Phase and Ground Current
Inputs:
Nominal Currents: 1 A / 5 A
Max. Measuring Range: Up to 40 x In (phase currents)
Up to 25 x In (ground current standard)
Capacity:
Overcurrent Proof:
4 x In/continuously
30 x In / 10 s
100 x In / 1 s
250 x In / 10 ms (1 half-wave)
Power Consumption: Phase current inputs
At In = 1 A S = 25 mVA
At In = 5 A S = 90 mVA
Ground current input
At In = 1 A S = 25 mVA
At In = 5 A S = 90 mVA
Sensitive Ground Current
Inputs:
Nominal Currents: 1 A / 5 A with 50:0.025 core balance CT
Max. Measuring Range: Up to 2.5 x In
Capacity:
Overcurrent Proof:
2 x In/continuously
10 x In / 10 s
25 x In / 1 s
100 x In / 10 ms (1 half-wave)
Power Consumption: At 1 A S = 550 mVA
At 0.1 A S = 7 mVA
At 5 A S = 870 mVA
At 0.5 A S = 10 mVA
Frequency Range: 50 Hz / 60 Hz ±10%
Terminals: Screw-type terminals with integrated short-circuiters (contacts)
www.eaton.com 643