EasyManuals Logo

Eaton EDR 3000 User Manual

Eaton EDR 3000
770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #668 background imageLoading...
Page #668 background image
EDR-3000 IM02602003E
Electrical Discharge Immunity Test (ESD)
IEC 60255-22-2
IEC 61000-4-2
class 3
Air discharge
Contact discharge
8 kV
6 kV
Radiated Radio Frequency Electromagnetic Field Immunity Test
IEC 60255-22-3
IEC 61000-4-3
26 MHz – 80 MHz
80 MHz – 1 GHz
1 GHz – 3 GHz
10 V/m
35 V/m
10 V/m
Immunity to Conducted Disturbances Induced by Radio Frequency Fields
IEC 61000-4-6
class 3
150kHz - 80MHz 10 V
Power Frequency Magnetic Field Immunity Test
IEC 61000-4-8
class 4
continuous
3 sec
30 A/m
300 A/m
EMC Emission Tests
Radio Interference Suppression Test
IEC/CISPR22
IEC60255-26
DIN EN 55022
150kHz - 30MHz Limit value class B
Radio Interference Radiation Test
IEC/CISPR22
IEC60255-25
DIN EN 55022
30MHz - 1GHz Limit value class B
www.eaton.com 656

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton EDR 3000 and is the answer not in the manual?

Eaton EDR 3000 Specifications

General IconGeneral
BrandEaton
ModelEDR 3000
CategoryRelays
LanguageEnglish

Related product manuals