EDR-3000 IM02602003E
Technical Data
Use Copper conductors only, 75°C (167°F).
Conductor size AWG 14 [2.5 mm].
Climatic Environmental Conditions
Storage Temperature: -30°C to +70°C (-22°F to 158°F)
Operating Temperature: -20°C to +60°C (-4°F to 140°F)
Permissible Humidity at Ann. Average: <75% rel. (on 56d up to 95% rel.)
Permissible Installation Altitude: <2,000 m (6,561.67 ft) above sea level
If 4,000 m (13,123.35 ft) altitude applies, a changed
classification of the operating and test voltages may be
necessary.
Degree of Protection EN 60529
HMI Front Panel with Seal: IP54
Rear Side Terminals: IP20
Routine Test
Insulation Test Acc. to IEC60255-5: All tests to be carried out against ground and other input and
output circuits.
Aux. Voltage Supply, Digital Inputs,
Current Measuring Inputs, Signal Relay
Outputs:
2.5 kV (eff.) / 50 Hz
Voltage Measuring Inputs: 3.0 kV (eff.) / 50 Hz
All Wire-Bound Communication
Interfaces:
1.5 kV DC
www.eaton.com 641