EasyManuals Logo

Eaton EDR 3000 User Manual

Eaton EDR 3000
770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #629 background imageLoading...
Page #629 background image
EDR-3000 IM02602003E
Decommissioning – Removing the Plug from the Relay
Dismounting the relay will lead to a loss of the protection functionality. Ensure
that there is a back-up protection. If you are not aware of the consequences of
decommissioning the device – STOP! DO NOT start.
Inform SCADA before you start.
Switch-off the power supply.
Ensure that the cabinet is de-energized and that there are no voltages that
could lead to injury of personnel.
Disconnect the terminals at the rear-side of the device. DO NOT pull any cable
pull on the plug! If it is stuck, use a screw driver.
Fasten the cables and terminals in the cabinet by means of cable clips to
ensure that no accidental electrical connections are caused.
Hold the device at the front-side while removing the mounting nuts.
Remove the device carefully from the cabinet.
In case no other device is to be mounted or replaced, cover/close the cut-out in
the front-door.
Close the cabinet.
www.eaton.com 617

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton EDR 3000 and is the answer not in the manual?

Eaton EDR 3000 Specifications

General IconGeneral
BrandEaton
ModelEDR 3000
CategoryRelays
LanguageEnglish

Related product manuals