Eaton EDR 3000 - Instantaneous Current Curves (Ground Current Calculated)

Eaton EDR 3000
770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-3000 IM02602003E
Instantaneous Current Curves (Ground Current Calculated)
The following characteristics is available:
DEFT (definite time).
Explanation:
The ground current can be measured either directly via a zero sequence transformer or detected by a residual
connection. The ground current can alternatively be calculated from the phase currents; but this is only possible if the
current transformers are Wye-connected.
www.eaton.com 688
t = Tripping delay
IG = Fault current
Pickup = If the pickup value is exceeded, the module/element starts to time out to trip .