EDR-3000 IM02602003E
Environmental Tests
Classification:
IEC 60068-1 Climatic
Classification
20/060/56
IEC 60721-3-1
Classification of ambient conditions (Sto-
rage)
1K5/1B1/1C1L/1S1/1M2
but min. -30°C (-22°F)
IEC 60721-3-2 Classification of ambient conditions
(Transportation)
2K2/2B1/2C1/2S1/2M2
but min. -30°C (-22°F)
IEC 60721-3-3 Classification of ambient conditions
(Stationary use at weather protected
locations)
3K6/3B1/3C1/3S1/3M2
but min. -20°C (-4°F) /max 60°C
(140°F)
Test Ad: Cold
IEC 60068-2-1 Temperature
Test duration
-20°C (-4°F)
16 h
Test Bd: Dry Heat
IEC 60068-2-2 Temperature
Relative humidity
Test duration
60°C (140°F)
<50%
72 h
Test Cab: Damp Heat (Steady State)
IEC 60255 (6.12.3.6)
IEC 60068-2-78
Temperature
Relative humidity
Test duration
60°C (140°F)
95%
56 days
Test Db: Damp Heat (Cyclic)
IEC 60068-2-30 Temperature
Relative humidity
Cycles (12 + 12-hour)
60°C (140°F)
95%
2