Eaton EDR 3000 - Resets; Collective Acknowledgments for Latched Signals:

Eaton EDR 3000
770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-3000 IM02602003E
Resets
Collective Acknowledgments for Latched Signals:
Collective Acknowledgments
LEDs Relay Outputs SCADA Pending
Trip Command
LEDs+
Relay Outputs+
SCADA+
Pending
Trip Command
Via PowerPort-E
or at the
panel
all...
can be
acknowledged.
At the panel, the
[Operation\
Acknowledge]
menu can directly
be accessed via
the »C« key.
All LEDs at once:
Where?
[Operation\
Acknowledge]
All Relay Outputs
at once:
Where?
[Operation\
Acknowledge]
All SCADA signals
at once:
Where?
[Operation\
Acknowledge]
All pending trip
commands at
once:
Where?
[Operation\
Acknowledge]
All at once:
Where?
[Operation\
Acknowledge]
External
Acknowledg-
ment*:
Via a signal from
the assignment
list (e.g.: a digital
Input)
all
... can be
acknowledged.
All LEDs at once:
Where?
Within the
Ex Acknowledge
menu.
All Relay Outputs
at once:
Where?
Within the
Ex Acknowledge
menu.
All SCADA signals
at once:
Where?
Within the
Ex Acknowledge
menu.
All Pending Trip
commands at
once:
Where?
Within the
Ex Acknowledge
menu.
All at once:
Where?
Within the
Ex Acknowledge
menu.
*The External Acknowledgement might be disabled if parameter »
Ex Acknowledgement«
is set to »
inactive«
within
menu [Device Para/Ex Acknowledge]. This blocks also the acknowledgement via Communication (e.g. Modbus).
www.eaton.com 194