EDR-3000 IM02602003E
Specifications of the Measured Value Acquisition
Phase and Ground Current Measuring
Frequency Range: 50 Hz / 60 Hz ± 10%
Accuracy: Class 0.5
Amplitude Error if I < In: ±0.5% of the rated current
*3)
Amplitude Error if I > In: ±0.5% of the measured current
*3)
Amplitude Error if I > 2 In: ±1.0% of the measured current
*3)
Harmonics: Up to 20% 3rd harmonic ±2%
Up to 20% 5th harmonic ±2%
Frequency Influence: <±2% / Hz in the range of ±5 Hz of the configured nominal frequency
Temperature Influence: 1% within the range of 0°C to +60°C (+32°F to +140°F)
*3
)
For earth current sensitive the precision does not depend on the nominal value but is referenced to 100 mA (with In =1 A) respectively. 500 mA
(with In = 5 A)
www.eaton.com 661