EDR-3000 IM02602003E
Configuration of the Average Value Calculation
Configuration of the Current Based Average Value Calculation* 
*=Availability depends on the ordered device code.
Current based Average Values and Peak Values
Time period for the 
calculation of the 
average and peak values
Start options
Reset of the average and 
peak values
Configuration Options
Where to configure?
In [Device Para\
Statistics\
Demand\
Current Demand]
sliding:
(sliding: average calculation 
based on sliding period)
fixed:
(fixed: Average calculation is 
resetted by the end of the period, 
that means with the next starting 
period)
duration:
(fixed or sliding period)
Start Fct:
(The average values are 
calculated based on the time 
period between two rising edges 
ot this signal)
Res Fc
(e.g. via Digital Input in order to 
reset the average values in 
advance (before the next rising 
edge of the start signal). This 
applies to option „Start FC“ only.
Trip (command) option to limit 
the average current demand: 
Yes
Please refert to chapter „System Alarms“
View average values and peak 
values
Where? Within menu [Operation\Statistics\Demand]
www.eaton.com 178