EasyManuals Logo

Eaton EDR 3000 User Manual

Eaton EDR 3000
770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #443 background imageLoading...
Page #443 background image
EDR-3000 IM02602003E
51X INV Measured Ground Fault Protection
Elements
51X[1] ,51X[2]
All ground current elements are identically structured.
For each element the following characteristics are available:
NINV (IEC/XInv);
VINV (IEC/XInv);
LINV (IEC/XInv);
EINV (IEC/XInv);
MINV (ANSI/XInv);
VINV (ANSI/XInv);
EINV (ANSI/XInv);
Thermal Flat;
IT;
I2T; and
I4T.
For tripping curves please refer to the “Appendix/Time Current Curves (Ground Current)” section.
The ground current can be measured either directly via a zero sequence transformer or detected by a residual
connection. The ground current can alternatively be calculated from the phase currents. However, this is only possible
if the current transformers are Wye-connected.
www.eaton.com 431

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton EDR 3000 and is the answer not in the manual?

Eaton EDR 3000 Specifications

General IconGeneral
BrandEaton
ModelEDR 3000
CategoryRelays
LanguageEnglish

Related product manuals