EDR-3000 IM02602003E
Protection Module Input States
Name Description Assignment via
ExBlo1-I Module Input State: External Blocking1 [Protection Para
/Global Prot Para
/Prot]
ExBlo2-I Module Input State: External Blocking2 [Protection Para
/Global Prot Para
/Prot]
Protection Module Signals (Output States)
Signal Description
Available Signal: Protection is available.
Active Signal: Active
ExBlo Signal: External Blocking
Pickup Phase A Signal: General Pickup Phase A
Pickup Phase B Signal: General Pickup Phase B
Pickup Phase C Signal: General Pickup Phase C
Pickup IX or IR Signal: General Pickup - Ground Fault
Pickup Signal: General Pickup
Trip Phase A Signal: General Trip Phase A
Trip Phase B Signal: General Trip Phase B
Trip Phase C Signal: General Trip Phase C
Trip IX or IR Signal: General Trip Ground Fault
Trip Signal: General Trip
Res Fault a Mains No Signal: Resetting of fault number and number of grid faults.
www.eaton.com 359