EDR-3000 IM02602003E
Device Planning Parameters of the Demand Management
Parameter Description Options Default Menu path
Mode Mode Do not use,
Use
Use [Device Planning]
Signals of the Demand Management (States of the Outputs)
Signal Description
Active Signal: Active
ExBlo Signal: External Blocking
Alm Current Demd Signal: Alarm Current demand value
Alarm I THD Signal: Alarm Total Harmonic Distortion Current
Trip Current Demand Signal: Trip Current demand value
Trip I THD Signal: Trip Total Harmonic Distortion Current
Global Protection Parameter of the Demand Management
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [SysA
/General Settings]
ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
1..n, Assignment
List
-.- [SysA
/General Settings]
Alarm Alarm Inactive,
Active
Inactive [SysA
/Demand
/Current Demand]
Threshold Threshold (to be entered as primary value) 10 - 500000A 500A [SysA
/Demand
/Current Demand]
www.eaton.com 191